What Are the Fire Safety (England) Regulations 2022?

The Fire Safety (England) Regulations 2022 (the Regulations) are designed to implement the recommendations of the Grenfell Tower Inquiry Phase 1 report. The Regulations will come into force on 23 January 2023..

The Regulations apply to England only. Most of the requirements set out in the Regulations are imposed on the responsible person (RP), which RPs need to plan and prepare for ahead of the Regulations coming into force.

The regulations require RPs in multi-occupied residential buildings to take specific actions, depending on the height of the building: some provisions apply regardless of height, more are needed once a building reaches 11 metres, and further requirements are introduced when a building reaches 18 metres (or 7 storeys) or more.

What Are the Requirements on The Fire Safety (England) Regulations 2022?

Information to residents – fire safety instructions (Regulation 9)

Provide relevant fire safety instructions to their residents, which will include instructions on how to report a fire and any other instruction which sets out what a resident must do once a fire has occurred, based on the evacuation strategy for the building.

Information to residents – fire doors (Regulation 9)

Provide residents with information relating to the importance of fire doors in fire safety.

Fire door checks (Regulation 9)

Undertake annual checks of flat entrance doors and quarterly checks of all fire doors in the common parts.

Secure information box (regulation 4)

Install and maintain a secure information box in their building. This box must contain the name and contact details of the Responsible Person and hard copies of the building floor plans.

Design and materials of external walls (regulation 5)

Provide to their local Fire and Rescue Service information about the design and materials of a high-rise building’s external wall system and to inform the Fire and Rescue Service of any material changes to these walls. Also, they will be required to provide information in relation to the level of risk that the design and materials of the external wall structure gives rise to and any mitigating steps taken.

Floor plans and building plan (regulation 6)

Provide their local Fire and Rescue Service with up-to-date electronic building floor plans and to place a hard copy of these plans, alongside a single page building plan which identifies key firefighting equipment, in a secure information box on site.

Lifts and essential fire-fighting equipment (regulation 7)

Undertake monthly checks on the operation of lifts intended for use by firefighters, and evacuation lifts in their building and check the functionality of other key pieces of firefighting equipment. They will also be required to report any defective lifts or equipment to their local Fire and Rescue Service as soon as possible after detection if the fault cannot be fixed within 24 hours, and to record the outcome of checks and make them available to residents.

Wayfinding signage (regulation 8)

To install signage visible in low light or smoky conditions that identifies flat and floor numbers in the stairwells of relevant buildings.

What Requirements Do the Responsible Persons Need to Apply?

Residential buildings with 2 or more domestic premises with common areas

  • Information to residents – fire safety instructions (Regulation 9)
  • Information to residents – fire doors (Regulation 9)

    Residential buildings between 11m and 17.9m in height

  • Information to residents – fire safety instructions (Regulation 9)
  • Information to residents – fire doors (Regulation 9)
  • Fire door checks (Regulation 9)

    Residential buildings 18m (or 7 storeys) and above in height

  • Information to residents – fire safety instructions (Regulation 9)
  • Information to residents – fire doors (Regulation 9)
  • Fire door checks (Regulation 9)
  • Secure information box (regulation 4)
  • Wayfinding signage (regulation 8)
  • Lifts and essential fire-fighting equipment (regulation 7)
  • Design and materials of external walls (regulation 5)
  • Floor plans and building plan (regulation 6)

    How Do I Meet the Requirements?

    Information to residents – fire safety instructions (Regulation 9)

    Responsible persons should display these instructions clearly in their building’s communal areas (such as the building’s lobby or any conspicuous part of the building) and share directly with residents when they move into the building. This information will need to be re-provided in both the communal area and to residents when a document is updated. This information must also be re-provided to residents on an annual basis.

    As is set out in the fire safety in purpose-built blocks of flats guidance a multi-occupied residential building is likely to have either a stay put or a simultaneous evacuation strategy.

    Information to residents – fire doors (Regulation 9)

    The information given to residents should cover the importance of keeping doors closed, that doors and self-closing devices are not tampered with and that any faults or damage to doors should be raised immediately.

    Residents will receive this information when they move into a multi-occupied residential building and then on an annual basis.

    Fire door checks (Regulation 9)

    Responsible persons for all multi-occupied residential buildings in England with storeys over 11 metres in height to:

  • undertake quarterly checks of all fire doors (including self-closing devices) in the common parts
  • undertake – on a best endeavour basis – annual checks of all flat entrance doors (including self-closing devices) that lead onto a building’s common parts.

    Secure information box (regulation 4)

    The regulations will require the responsible person to install a suitably secure information box in or on their high-rise building. They will also be required to provide in the box:

  • Their UK contact details
  • The UK contact details of any other person who has the facilities to and is permitted to access the building as the responsible person considers appropriate
  • Copies of the building’s floor plans – which identify specified key fire-fighting equipment
  • A single page block plan – which identifies specified key fire-fighting equipment

    Access should be given to the fire and rescue service. Boxes should be maintained, and their contents kept up to date in line with the duties imposed by the regulations and the Fire Safety Order.

    Design and materials of external walls (regulation 5)

    Responsible persons of existing high-rise residential buildings in England to provide their local fire and rescue service with information about the design and materials of the building’s external walls and to inform their local fire and rescue service of any material changes made to them. Supporting guidance will specify the type of information required by fire and rescue service to support their operational response and how this should be shared.

    Responsible persons will also be required to provide additional information to their local fire and rescue service in relation to the level of risk of spread of fire that the external wall structure (its design and materials) pose and the steps they (responsible person) have taken to mitigate these risks.

    The above information should be shared in a standard format and a template for responsible persons will be provided in supporting guidance.

    Floor plans and building plan (regulation 6)

    Responsible persons of high-rise residential buildings[footnote 1]: in England to draw up and share electronically up-to-date floor plans identifying the location of key fire-fighting equipment with their local fire and rescue services. A plan will need to be prepared for each floor, but where floors are identical only one plan needs to be produced.

    The responsible person will also be required to provide their local fire and rescue services with an additional single page building plan which should include the location of all key fire-fighting equipment. The plans should be simple, to assist quick and critical decisions taken by operational fire-fighters during an incident.

    Lifts and essential fire-fighting equipment (regulation 7)

    Responsible persons in high-rise residential buildings[footnote 1] to undertake additional monthly checks of any lifts within the building that are designed, installed and maintained to be used by fire-fighters (with the addition of evacuation lifts) and of the mechanism which allows fire-fighters to take control of lifts. Monthly checks will also be required on all evacuation lifts. Checks at the same frequency will be applied to key fire-fighting equipment (which is defined in the regulations).

    Where responsible persons identify, either through the monthly checks or via any other routine checks, that a relevant lift or mechanism has a fault or is out of service, they must report it to the local fire and rescue service electronically. Responsible persons will be required to record the outcome of these monthly checks in an open and transparent way that is accessible to residents (for example by posting them on a notice board or making them available to a resident’s association).

    Under the Fire Safety Order checks on lifts and the equipment should already be taking place. These Regulations add to, they do not replace, responsible persons existing duties under the Fire Safety Order. All lifts including secondary or back up power supplies as well as any other fire-fighting equipment should already be subject to a suitable programme of maintenance and inspection.

    Wayfinding signage (regulation 8)

    To install signage visible in low light or smoky conditions that identifies flat and floor numbers in the stairwells of relevant buildings

    .

    Signage should conform to the specifications and location set out in paragraph 15.14 to 15.16 of Approved Document B Volume 1 2019 edition incorporating 2020 amendments.

  • Unlock the true value of our services with our affordable pricing options!

    Customer reviews

    Excellent on Checkatrade and Google
    4.5/5

    Frequently asked questions:

    Q: How thick are your fire doors?

    Our 30 minute fire doors (FD30) are 44mm thick

    Our 60 minute fire doors (FD60) are 54mm thick

    Q: How much can be removed from each edge of a fire door?

    The amount that can be removed from the edges of a fire door differs from one door to the next and depends on several factors, including the exact materials used during construction and guidelines from the fire rating certificate. Accurate trimming information can only be provided by the manufacturer on a case-by-case basis after the door has been completed.

    Q: How long do fire doors last?

    There are no set rules that detail how long a fire door lasts before it needs to be replaced. The condition of the door should be monitored and checked at least every 6 months to ensure it is in good working order. Fire doors should comply with the latest fire door regulations and so it is important to keep up to date with any changes in regulations which may mean your doors are no longer fit for purpose.

    Q: Do your fire doors satisfy disability regulations?

    All our fire doors satisfy the DDA regulations.

    Q: How do you calculate the weight of a fire door?

    In order to calculate the weight of a fire door you will need to know the weight per square meter (kg/m2) of the doors core. This is determined using the thickness of the door as follows: 44mm = 55kg 54mm = 75kg The calculation below can be used to determine the approximate weight of the fire door. Please note that the calculation does not take glass weight into account. Width X height X thickness X kg/m2 of the door’s core = Weight of fire door. For example for a door that was 926x2040mm with a thickness of 44mm the following calculation would give an approximate weight: 0.926 X 2.040 X 0.44 X 55 = 45 KG.

    Q: Can I update existing fire doors that have no seals to conform to regulations?
    Yes, fire door seals can be fitted to either the door or the frame Double doors or door and a half fire doors will need to have fire door seals fitted to the door to ensure that the gap between each leaf is taken into consideration.
    Q: What are closing force ratings for fire door closers?
    The closing force rating of fire door closers, also called “power size”, relates to the maximum width and weight of fire doors that the door closer can reliably close and hold closed.
    Q: Can a fire door be fitted with self closing hinges?
    Whilst it is possible to fit self closing hinges to a fire door, Safelincs does not recommend their use as they slam the door quickly.
    Q: Can I wedge my fire door open?
    Fire doors should never be propped or wedged open as the fire door would not be able to close in the event of a fire. A safe and legal solution to holding open fire doors is to install a fire door holder also known as a retainer. Fire door retainers can be easily installed onto existing doors and allow the door to be held open at any angle. They comply with regulations because when the fire alarm sounds, the door retainer releases the fire door to close, preventing the spread of fire. Fire doors should never be propped or wedged open to improve ventilation.
    Q: Can I cut the bottom off my fire door to increase air circulation?
    Cutting the bottom off a fire door could threaten the integrity of your fire door and could put lives at risk. If you need to increase air circulation in your building the best option is to hold your fire door open with a fire door holder or free-swing door closer. These are legal solutions that enable a fire door to be left open but will activate the automatic closing of the fire door on the sounding of fire alarm, preventing the spread of smoke and fire.
    Q: Can you make alterations or drill holes in a fire door?
    Yes, in some cases you can make alterations to your fire door, however these alterations can only be done if they remain within the scope of the fire door’s Certifire Approal documents. For example when a fire rated door viewer or intumescent letterbox / letter plate is required. This information should also be detailed in the installation and maintenance instructions supplied with each door leaf. It is critical that any changes made to a fire door is done so following the manufacturer’s instructions, by a trained professional, and with certified hardware to ensure that the performance of the door, and it’s associated certification, is not compromised. BWF-Certifire have created a guide on how to ensure you retain your Fire Door Certification when considering making alterations.
    Q: Are intumescent strips required on fire doors?
    Yes, intumescent fire seals are required on all fire doors. Newer doors and frames have a channel cut into them for rebated seals (if not supplied with seals already in place). For older doors, surface-mounted seals can be used instead. Please note: some of our seals have brushes on them, which are designed to block the spread of smoke around the door before ambient heat has caused the intumescent seals to expand and fill any gaps – these are usually required on doors, so make sure a competent person has performed the appropriate fire risk assessments or fire door inspections before purchasing.
    Q: Which rooms need fire doors?
    Fire doors must be used in walls which form the compartmentation of the premises – specific areas within the building that are constructed to be fire-resistant. These may be individual rooms, but could also contain multiple rooms or might be vertical risers and lift shafts. Fire-rated doors are not required for walls not part of a compartment boundary. Additional fire doors can be installed in place of normal doors, but they would provide minimal protection as the walls around them may not be constructed of especially fire-resistant materials and could burn through while the fire door remains intact. There is a risk of occupants gaining a false sense of security if fire doors are installed in non-compartment walls, so this should only be done under the guidance of a proper fire risk assessment conducted by a competent person. Please consult the original building plans, if available, to determine where your premises’ fire compartments are, or otherwise have a competent person perform a fire risk assessment or fire door inspection.
    Q: How do you stop fire doors slamming?
    Regulations state that fire doors should self-close completely and reliably. They do not however need to bang or slam shut. The reason for the slamming is usually due to the fire door closer having an incorrect closing speed or power size. Many self-closing devices can be adjusted so that the door will close correctly without slamming shut. Other issues including a loss of fluid or improper fitting could be causing the issue. It is also possible to fit self-closing devices with a latching action which close the door quickly at first and then stop it from slamming by closing the last few inches slowly. It is advisable to have your fire door closer maintained and altered by a competent person.